8 Parameter list
8.4 Parameter groups for RASP5
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
189
8.4.7 Parameter group 6 (Extended motor control)
Table 46:
Parameter group 6 (Extended motor control)
Parameter
Designation
Description
Unit
Min
Max
DS
P6-01
Motor control mode
Motor control mode
An autotune must be performed if setting 1 / 2 / 3 / 4 / 5 is
used
0: Smart-Vector Speed Control
1: Speed Control with Torque Limit (vector)
2: PM motor speed control
3: LSPM motor speed control
4: SyncRel motor speed control
5: Brushless DC motor speed control
6: Speed control (enhanced V/f)
–
0
6
0
P6-02
MSC Kp
Proportional gain Kp at Motor Speed Control
(P6-01 = 0, 1, 2, 3, 4, 5)
%
0.0
400.0
50.0
P6-03
MSC1 Ti
Integral time Ti at Motor speed Control
(P6-01 = 0, 1, 2, 3, 4, 5)
s
0,010
1.000
0,050
P6-04
M-Max Motoring
M-Max Motoring
When working in Vector mode (P4-01 = 1) this parameter
defines the max. torque limit. In the other control modes, this
parameter specifies the current limit.
%
0
200%
150%
P6-05
Action@Underload
Motor
Device reaction after occuring of “Underload Motor”.
Possibilities device dependent
0: deactivated
2: Trip (stop)
–
0
1
0
P6-06
M-Min (f-Ref>5Hz)
Limit
Minimum torque required, when the output frequency is
above 5 Hz in the motor range
%
10
150
50
P6-07
M-Min (f>P1-09) Limit
Minimum torque required when the output frequency is
above the field weakening point.
%
5
150
10
P6-08
Change Phasese-
quence Motor
Changes the sequence of the output phases.
This prevents two phases of the motor cable having to be
changed in case the motor runs in the wrong direction.
0: U–V–W (clockwise rotating field)
1: U–W–V (counterclockwise rotating field)
Note:
Only for RASP5… and RAMO5-W…
–
0
1
0
P6-09
T-Memory Enable
When enabled, the motor thermal memory retention function
will save the calculated motor thermal history on drive power
down, using this saved value as the starting value on next
power up. If this function is disabled, the motor thermal
history is reset to zero on every power up.
0: Thermal memory OFF
1: Thermal memory ON
–
0
1
1
P6-10
Action @I-Current-
Limit
0: deactivated - motor overload management switched off
1: activated - speed decrease
The output torque is reduced to avoid overload.
P6-11
EnhancedGenerator-
Control
Adaptation of regenerative operation
Adaptation of the motor model in vector mode and with PM
motors to achieve a better performance of the drive when
regenerating.
0: disable
1: enable
–
0
1
0