7 Parameterization
7.2 Parameterization using OLED operating unit
162
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
7.2.2 Set parameters
Table 31:
Modify parameters
Commands
Description
Press the
OK
button and hold it down for two seconds in order to access
the parameter interface.
->
The display shows the parameter that was used last.
Select the parameters using the
▲
and
▼
buttons.
Press the
OK
button.
The value of the selected parameter can be changed.
Change the parameters using the
▲
and
▼
buttons.
Press the
OK
button to confirm the parameter value change.
As soon as the parameter is displayed, the value will have been saved.
Press the
OK
button and hold it down for two seconds in order to exit the
parameter interface (display:
Stop
).
Switching between two parameter groups
The parameters are in sequential order.
In other words:
Moving forward from the last parameter in a parameter group will take
you to the first parameter in the next parameter group and vice versa.
Note:
To access the extended parameter groups, you will need to enter the
password in parameter P1-14 (default setting: level 2 = 101).
Press the
▲
and
STOP
buttons to jump to the first parameter in the next
parameter group.
Press the
▼
and
STOP
buttons to jump to the first parameter in the
previous parameter group.