9 Communication
9.2 EtherNet / IP
230
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
9.2.16.2 RASP5
Table 56:
Acyclic parameters for RASP5
Parameters
De
signa
tion
Instan
ce
Ac
cess righ
t
Ob
ject class
Ser
vic
e cod
e
Read
Ser
vic
e cod
e
W
rite
Leng
th (w
or
d)
D
ata for
m
at
Value
ra
ng
e
Scaling
De
fault
setting
–
PDI1 control word
1
R/W
0x04
0x18
0x19
1
Word
–
–
–
–
PDI2 speed reference value
2
R/W
0x04
0x18
0x19
1
S16
–
–
–
–
PDI3 fieldbus ramp time
3
R/W
0x04
0x18
0x19
1
U16
–
–
–
–
PDI4 dummy - reserved
4
R/W
0x04
0x18
0x19
1
U16
–
–
–
–
Speed reference value (internal
format)
5
R/W
0x04
0x18
0x19
1
S16
–
–
–
SW
(P0-03)
Status word
6
R
0x04
0x18
–
0
U16
–
–
–
P0-07
Output frequency
7
R
0x04
0x18
–
0
S16
-5000 - 5000
500
≙
50.0 Hz
–
(P0-09)
PDO3 motor current (P5-05, selec-
table)
8
R
0x04
0x18
–
0
U16
0 - 65535
10
≙
1.0 A
–
(P0-21)
PDO4 heat sink temperature
(P5-06, selectable)
9
R
0x04
0x18
–
0
U16
–
–
–
P0-10
Motor Power Rel
10
R
0x04
0x18
–
0
U16
0 - 65535
100
≙
1.00 kW
–
–
Fault message
11
R
0x04
0x18
–
0
U16
–
–
–
P0-29
Drive size/rating
12
R
0x04
0x18
–
0
U16
0 - 65535
–
–
P0-29
Power@Ue
13
R
0x04
0x18
–
0
U16
0 - 65535
100
≙
1.00
–
–
Voltage rating
14
R
0x04
0x18
–
0
U16
–
–
–
P0-28
Application Version
15
R
0x04
0x18
–
0
U16
0 - 65535
100
≙
1.00
–
System Version
16
R
0x04
0x18
–
0
U16
0 - 65535
100
≙
1.00
–
P0-29
DeviceType
17
R
0x04
0x18
–
0
U16
0 - 65535
–
–
–
Scope channel 1 - data
18
R
0x04
0x18
–
0
U16
–
–
–
–
Scope channel 2 - data
19
R
0x04
0x18
–
0
U16
–
–
–
–
AI1
20
R
0x04
0x18
–
0
U16
–
–
–
P0-02
Thermistor input1
21
R
0x04
0x18
–
0
U16
0 - 1
–
–
P0-04
f-PreRamp
22
R
0x04
0x18
–
0
S16
-5000 - 5000
500
≙
50.0 Hz
–
P0-20
DC-Link voltage
23
R
0x04
0x18
–
0
U16
0 - 65535
100
≙
100 V DC
–
P0-21
Heatsink temperature
24
R
0x04
0x18
–
0
S16
-500 - 1500
10
≙
1.0 °C
–
P0-30
Serial number
25
R
0x04
0x18
–
0
U16
0 - 65535
–
–
26
R
0x04
0x18
–
0
U16
0 - 65535
–
–
27
R
0x04
0x18
–
0
U16
0 - 65535
–
–
28
R
0x04
0x18
–
0
U16
0 - 65535
–
–
–
Output relay status
29
R
0x04
0x18
–
0
U16
–
–
–
–
Reserved
30
R
0x04
0x18
–
0
U16
–
–
–
–
Reserved
31
R
0x04
0x18
–
0
U16
–
–
–
P0-26
kWh Meter
32
R
0x04
0x18
–
0
U16
0 - 65535
10
≙
1.0 kWh
–
P0-27
MWh Meter
33
R
0x04
0x18
–
0
U16
0 - 65535
1
≙
1 MWh
–