2.15 Thermistor and motor cable monitoring
In RAMO5 and RASP5, the reaction of the thermistor fitted in the motor and
the motor cable are set using parameter P2-27.
Table 16:
Parameter P2-27 for thermistor and motor cable monitoring
a
Bridge in the motor connector:
Only monitors the plugged-in status of the motor
connector.
b
Bridge in the motor terminal box:
Monitors the plugged-in status of the motor connector and
the motor cable connection.
c
Thermistor connection:
Monitors the plugged-in status of the motor plug, the motor
cable connection, and the thermistor (or temperature
switch, Thermo-Click) in the motor.
Figure 36:
Thermistor monitoring
Para-
meter
Designation
Description
Unit
Min
Max
DS
P2-27
Action@
Motor thermistor
fault
Device response (depending on device)
after “Thermistor Fault” occurs.
0: Disabled (OFF)
1: Enabled (ON)
–
0
1
1
ATTENTION
The setting of parameter P2-27 may only be changed by trained
specialist personnel!
5
8
1
7
3
PE
T1
T2
M 3 ∼
ϑ
U
V
W
PE
①
②
③
P2-27