9 Communication
9.2 EtherNet / IP
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
207
9.2.4.1 NS LED (“network status”)
The
NS
LED (network status) is used to indicate network statuses.
9.2.4.2 MS LED (“module status”)
The
MS
(module status) LED indicates the status of the Rapid Link 5 module.
9.2.4.3 E/IP P1 and E/IP P2 LEDs
The
E/IP P1
and
E/IP P2
LEDs indicate the status of general communication.
LED state
Description
Off
No supply voltage or IP address not assigned
Green flashing
online, but no communication
Green illuminating
Connection to EtherNet/IP network established
Red flashing
Fault detected (e.g., connection request timeout)
illuminated red
Error detected (e.g., same IP address assigned twice)
Green-red flashing
Self-test/initialization
LED state
Description
Off
No supply voltage or device not turned on
Green flashing
Configuration error or module in standby mode
Green illuminating
Connection to EtherNet/IP controller established
Red flashing
A reversible error has occurred
1)
illuminated red
Fatal error detected
2)
Green-red flashing
Self-test/initialization
1) Reversible errors can be reset by means of a reset or by power cycling the supply voltage (turning it off and then
back on).
2) In contrast, fatal errors can only be reset by power cycling the supply voltage or by changing the hardware confi-
guration while the supply voltage is off, as the case may be.
LED state
Description
Off (green)
Port not connected
Off (yellow)
Data transfer
at 10 MBit/s active or no communication
Green illuminating
Port connected but no communication
Green flashing
Data transfer present and communication active
illuminated yellow
Data transfer active at 100 MBit/s