7 Parameterization
7.2 Parameterization using OLED operating unit
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
163
7.2.3 Reset parameters (RESET)
Table 32:
Resetting parameters (RESET)
7.2.4 Extended parameter set
Table 33:
Open and exit the extended parameter set
Commands
Description
Reset to default settings
+
+
Press the
▲
and
▼
and STOP buttons together or simultaneously and hold them down
for two seconds.
-> All parameters will be reset to their default settings.
The display will show
P-dEF
.
Reset after a fault
Press the
STOP
button to reset a fault message.
The display will show
StoP
.
Commands
Description
Open the extended parameter set
Press the
OK
button and hold it down for two seconds in order to
access the parameter interface.
->
The display shows the parameter that was used last.
Use the
▲
and
▼
buttons to select parameter P1-14.
Press the
OK
button.
Use the
▲
or
▼
buttons to select the password set using parameter
P2-32 (Level 2, default setting 101).
Press the
OK
button to confirm.
->
The extended parameter set is now available.
Exit the extended parameter set
Use the
▲
and
▼
buttons to set a value for P1-14 that does not match
the password (P2-32).
Press the
OK
button to confirm.
->
Only the basic parameters, i.e. the parameters in the first parameter
group (P1-01 to P1-14), will now be accessible.