
1 Rapid Link 5 system
1.4 Technical data
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
19
1.4 Technical data
Table 2:
General rated operational data (overview)
Technical data
Formula
symbol
Unit
Value
RAMO5
RASP5
General
Standards
IEC/EN 60947-4-2
EN 50581
IEC/EN 61800-3
IEC/EN 61800-5-1
EN 50581
EN 61800-5-2
EN ISO 13849-1
EN 62061
Approvals, certificates
CE, CCC, cUL
CE, cUL
Production quality
Directive 2011/65/EU (RoHS),
ISO 9001
Directive 2011/65/EU (RoHS),
ISO 9001
Protection class
IP65, NEMA 12 / NEMA 12K
IP65, NEMA 12 / NEMA 12K
Mounting position
vertical (
Ambient temperature range
Operation
°
C
-10 - +40
-10 - +40 (without derating)
Storage
°
C
-40 - +70
-40 - +70
Set-up altitude
H
m
0 to 2000 above MSL with 1 % power
reduction per 100 m over 1000 m
0 to 2000 above MSL with 1 % power
reduction per 100 m over 1000 m
Humidity (IEC/EN 50178)
p
w
%
< 95 relative humidity
non-condensing
< 95 relative humidity
non-condensing
Vibration (IEC/EN 60068-2-6)
Amplitude Hz
3 - 15.8
Vibration amplitude: 0.15 mm
3 - 15.8
Vibration amplitude: 0.15 mm
Acceleration
Hz
15.8 - 150 constant acceleration 2 g
15.8 - 150 constant acceleration 2 g
Mechanical shock resistance (IEC/EN
60068-2-27)
1000 shocks per shaft,
Semisinusoidal 15 g/11 ms
1000 shocks per shaft,
Semisinusoidal 15 g/11 ms