8 Parameter list
8.4 Parameter groups for RASP5
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
187
8.4.6 Parameter group 5 (Communication)
Table 45:
Parameter group 5 (Communication)
Parameter
Designation
Description
Unit
Min
Max
DS
P5-01
RS485-0 Address
Unique address of the drive (keypad, OP bus)
–
1
63
1
P5-02
COM Loss Timeout
With an active communication link, if a valid telegram is not
received by the drive within the period set with this para-
meter, the drive will react as set in P5-03.
s
0
5.0
2
P5-03
Action@Communica-
tion Loss
Device reaction after “Communication Loss” occurs.
Possibilities device dependent
0: Trip
1: Ramp to stop, then trip
2: Ramp to stop only (no trip)
3: Run at preset speed 2 (P2-01)
–
0
3
0
P5-04
FieldbusRampControl
Fieldbus Ramp Control
0: OFF. Ramps are controlled by internal drives parameters
1: ON. Ramps are controlled by the fieldbus.
–
0
1
0
P5-05
NETSendPZD3
Configuration of the 3rd process data word PDO-3 from the
drive to the network master during cyclic communication.
0: Motor current in A with one decimal place,
e.g. 100
≙
10.0 A
1: Output power in kW with two decimal places,
e.g. 400
≙
4.00 kW
2: Status of the sensor inputs (SEN I).
Bit 0 = status SEN II1, bit 1 = status SEN I2, etc.
3: Internal temperature. -500 - 1500
≙
-50 - 150 °C
–
0
6
0
P5-06
NETSendPZD4
Configuration of the 4th process data word PDO-3 from the
drive to the network master during cyclic communication.
0: Motor current in A with one decimal place,
e.g. 100
≙
10.0 A
1: Output power in kW with two decimal places,
e.g. 400
≙
4.00 kW
2: Status of the sensor inputs (SEN I).
Bit 0 = status SEN II1, bit 1 = status SEN I2, etc.
3: Internal temperature. -500 - 1500
≙
-50 - 150 °C
–
0
6
1
P5-07
NETReceivePZD3
Configuration of the 3rd process data word PDI-3 from the
network master to the drive during cyclic communication.
0: reserved
1: User defined ramp times, e.g. 500
≙
5.00 s.
–
0
3
1
P5-08
NETReceivePZD4
Configuration of the 4th process data word PDI-4 from the
network master to the drive during cyclic communication.
0: reserved
–
0
3
0