8 Parameter list
8.4 Parameter groups for RASP5
176
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
P0-24
t-Run PCB in OT
Time elapsed, in which the drive has operated with a high temperature
at the PCBs (ambient temperature)
Displays the time in hours and minutes above 80 °C.
The value is used for various internal protective functions.
hh:mm:ss
P0-25
f-PostRamp
Speed reference after the ramp
Hz/rpm
P0-26
kWh Meter
Energy consumption kWh Meter (not resettable)
Displays the energy consumption in kWh. When the value reaches 1000,
it is reset to 0 and the number of MWh in P0-27 is increased by 1.
The value cannot be reset and shows together with P0-27 the energy
consumption since the day of manufacture.
kWh
P0-27
MWh Meter
Energy consumption MWh Meter (not resettable)
Displays the energy consumption in kWh. The value cannot be reset and
shows together with P0-26 the energy consumption since the day of manu-
facture.
MWh
P0-28
Application Version
Application Version
Level 1: Application v checksum
Level 2: System v checksum
–
P0-28
System Version
System version
P0-29
n/a
Device information
–
NoOfInputPhases
Number of input phases
FrameSize
Frame size
kW/HP
Motor output
Power@Ue
Device Power at Device Voltage Rating
Device voltage
Device Voltage Rating
DeviceType
Device type
P0-30
Serial number
Serial Number of the device
–
P0-31
t-Run
Total operating time of the drive since the date of manufacture
Displayed in hours, minutes and seconds.
Pressing
Δ
on the drive keypad will change the display from “hours” to
“minutes and seconds”.
hh:mm:ss
P0-32
t-Run since Restart
Run time since power on or last Reset
Total operating time of the drive since the last trip occurred or power down
in hours, minutes and seconds.
Pressing
Δ
on the drive keypad will change the display from “hours” to
“minutes and seconds”.
hh:mm:ss
P0-33
t-Run since Trip
Total operating time of the drive since the last trip occurred
Displayed in hours, minutes and seconds.
Pressing
Δ
on the drive keypad will change the display from “hours” to
“minutes and seconds”.
hh:mm:ss
P0-34
t-HoursRun Enable
Total operating time of the drive since the last drive ENABLE signal was
applied
Displayed in hours, minutes and seconds.
Pressing
Δ
on the drive keypad will change the display from “hours” to
“minutes and seconds”.
hh:mm:ss
P0-35
Fan Runtime
Run time of the integrated fan (not resettable)
Displayed in hours. (F is displayed at the beginning of the line).
hh:mm:ss
P0-36
DC-Link Log
DC-Link voltage log
Displays the most recent 8 samples of the DC bus voltage prior to a drive
trip condition occurring. The sample interval is 256 ms.
V
Parameter
Designation
Description
Unit