Programming
84
02/09 AWB2723-1612en
• 1 = the SWD gateway also starts up without comparison
between the planned configuration and the target
configuration. This setting is conceived for CANopen
configurators that do not support downloading of the
planned module list to the gateway.
If a planned configuration is downloaded to the gateway, a
comparison of the configurations takes place.
• 0 = the comparison between planned configuration and
target configuration is mandatory (default setting).
Read access
Delivers back the currently valid setting.
Write access
Definition of the desired behaviour.
DiagFlags (0x2004)
Content
Via this entry the current status of the diagnostic flags in
accordance with table table 9 page 76 can be read out.
Read access
The current status of the diagnostic flags is returned.
Write access
Not permissible.
Delay between cyclic exchange (0x2010)
Content
Pause time between two SWD cycles in milliseconds
(0 - 255 ms)
Read access
Currently set pause time
Write access
Pause time to be set
At present this parameter cannot be changed.