Programming
30
02/09 AWB2723-1612en
Table 3:
Application parameters
Mode parameter
Value
Meaning
SmartWire Darwin baud
rate
125 kBit/s
The baud rate of the SmartWire Darwin
network. The value is a fixed setting and can
not be changed.
Compatible devices
allowed
No
The planned slaves in the PROFIBUS
configuration must comply with the slaves of
the stored gateway target configuration. If
not, no data interchange takes place with the
DP master.
Yes
Data interchange takes place, if the
SmartWire-Darwin slaves are compatible with
the DP configuration. This is displayed via the
status LED on the device.
All slaves optional
Defined for each slave
Specification is performed individually for
each slave (
individual SmartWire Darwin slaves")
Yes
Data transmission to the PROFIBUS also takes
place for a random number of failed
SmartWire-Darwin slaves.
The setting in the module parameters has no
effect.