Engineering
45
02/09 AWB2723-1612en
CANopen address setting
The gateway requires a unique address (node ID) in the
CANopen network. This is set on the gateway via DIP
switches (switches 2 - 8). Valid addresses are 2 - 32.
CANopen connection
Connection to the field bus is performed via a 9-pole D-SUB
socket
Figure 17: Configuration of the CANopen plug on the gateway
Baud Rates
The gateway supports operation on CANopen masters at up
to 1 MB. Adaptation to the baud rate of the network master
takes place automatically.
SUB-D plug
Signal
1
-
2
CAN_L
3
GND
4
-
5
-
6
GND
7
CAN_H
8
-
9
-
1
6
7
8
9
2
3
4
5