92
02/09 AWB2723-1612en
Meaning of the LED
indicators
Description
POW
Device ready for operation
on
Operating system firmware erroneous or
hardware defective
Off
Description
PROFIBUS status
LED
Data interchange between
the gateway and the PLC via
PROFIBUS
Cyclic data communication runs on the
PROFIBUS. The planned configuration
complies with the gateway target
configuration.
Green continuous
light
Yes
The DP master does not detect a data
interchange, because the planned
configuration does not comply with the
gateway target configuration
Flashing (green)
Yes
No communication takes place on the
PROFIBUS. No DP master is detected (for
example, on account of a wrong slave
address)
Off
No
Extended DP diagnostics:
The input data from SmartWire Darwin slaves
is invalid or the necessary slaves are missing.
Orange
yes
Description
CAN status LED
Data exchange gateway
via CANopen to PLC
CAN interface inactive.
Off
No
Baud rate detection active on the CAN bus
Red strobe light
No
CAN baud rate detected ,waiting for a valid
target configuration
Orange
No
Communication error on the CAN bus.
(Error warning level reached.)
Red flashing
yes