easySoft-CoDeSys
69
02/09 AWB2723-1612en
The following settings are possible:
Parameter name
Value (default)
Meaning
Device presence
(0 = optional; 1 =
mandatory)
(1)
The SmartWire Darwin slave must be present at
the start or in operation. If it is not addressable,
the entire SmartWire Darwin network is stopped.
Note: this is only effective, if the parameter "All
slaves optional"
in the general SWD network
settings has the value 0.
0
The SmartWire Darwin slave may be missing at
the start or in operation. Absence of the slave is
reported to the application. Communication
with the other slaves in the network remains
unchanged.
Q_byte…
0 - 255 (0)
The initial value of the outputs that is output
when the master starts, before the first data are
sent by the PLC to the slave.