easySoft-CoDeSys
65
02/09 AWB2723-1612en
Guarding mechanisms
Node guarding or heartbeat can be used to monitor
communication between the gateway and the CAN master.
Node guarding
Node guarding is supported. The monitoring interval (guard
time) and the number of repeat attempts can be set. Node
guarding is deactivated as standard.
Heartbeat
If the option
Activate heartbeat creation
is selected, the
module emits heartbeats at the millisecond intervals
specified in
Heartbeat producer time
. If the value is 0, the
function is deactivated.
The following illustration shows the register with the CAN
parameters.
h
The node guarding mechanism cannot be operated
together with the heartbeat monitoring.