Input/output addresses
39
02/09 AWB2723-1612en
Table 4:
Structure of the extended diagnosis
Example
A SmartWire-Darwin network consists of nine SmartWire-
Darwin slaves. If a short circuit is reported in a SmartWire-
Darwin slave EU5E-SWD-4D4D (input/output module with
overload message) that is the fifth slave in the network, the
diagnostics look as follows.
Byte
Value
Description
1
Ly
Length of detailed status message
2
0xA1
Status type
3
SmartWire Darwin slave address (1 - 58)
4
0
-
5
first detailed diagnostic message/status message
6
-
Ly
nth detailed diagnostic message/status message
Absolute
byte
Byte
Value
Description
1
1
0x8
V0-Status-1
2
2
0xC
V0-Status-2
3
3
0
V0-Status 3
4
4
1
DP master address
5
5
0x4D
Gateway ID
6
6
0x13
Gateway ID
Module status header
7
1
0xC
Length of module status
8
2
0x82
-
9
3
0x00
-
10
4
0x00
-
11
5
0x0
The SmartWire Darwin slaves 1
to 4 do not report a diagnosis.