Programming
86
02/09 AWB2723-1612en
Read access
Data are returned from the stored gateway target
configuration.
Write access
Data are written to the
Planned configuration
. The
writing may be performed only in “pre-operational” status.
The list of planned modules can be transferred from the CAN
master to the gateway via the entry “Module list (0x1027)".
Presence of device (0x2100)
These local entries define how the SWD gateway behaves, if
individual slaves are not found.
• Subindex = 0: number of slaves recognized on the SWD
network
• Subindex = 1 to number of SWD slaves: this entry defines
whether the corresponding slave is allowed to be missing
from the SmartWire-Darwin network (“optional”); in this
case the SWD network continues to run. Or whether the
slave is regarded as being necessary. If a slave is missing,
the SWD network is set to failsafe mode.
Settings:
• 0 = slave is allowed to be missing from the network =
“optional” slave.
• 1 = the slave is not allowed to be absent = “necessary”
slave. (Default setting).
Read access
Delivers back the currently valid setting for the specified
slave.
Write access
Desired setting for the specified slave.