Commissioning
20
02/09 AWB2723-1612en
Switching on for initial startup, a replacement or a
changed SmartWire Darwin configuration
Prerequisite for reading the configuration:
• All SmartWire Darwin slaves are connected to the
SmartWire Darwin line.
• The SmartWire-Darwin network is connected to the
gateway.
• The voltage POW is applied to the gateway and the power
LED lights up.
• The voltage AUX is applied (if necessary).
• The SmartWire-Darwin status LEDs of the SmartWire-
Darwin slaves are on or are flashing.
X
Press the configuration button on the gateway for at least
two seconds. The SmartWire status LED on the gateway
begins to flash orange. The SmartWire-Darwin status LEDs
on the SmartWire-Darwin slaves also flash.
All slaves are addressed in sequence, the complete
configuration is stored retentively (gateway target
configuration). The gateway is then restarted (see following
section).
j
Warning!
If a SmartWire-Darwin slave has failed, the SmartWire-
Darwin network can still be operated with the remaining
slaves, depending on the configuration setting (even after
a repeat power up of the gateway). The failure is reported
to the application.
If there is a faulty configuration and the configuration
button is pressed, only the slaves up to the failed device
are addressed and stored. Use of the remaining slaves is
not possible until the defective slave has been replaced
and the configuration has been read in again by pressing
the configuration button.