4 Commissioning
4.12 Acyclic data
DX-NET-PROFINET2-2
01/22 MN040062EN
www.eaton.com
91
The following table lists the parameter channel errors of the PROFIdrive pro-
file. The possible errors for the variable frequency drive/variable speed starter
are marked (column “DC1, DE1”).
Table 49:
Parameter channel errors with PROFIdrive
4
Format
Format: 44
hex
: Error
5
No. of Values
Number of values: 01
hex
6, 7, 8, 9
Error Number
Error number: 00
hex
- 23
hex
Error
number
[hex]
Designation
Description
Supplemen-
tary infor-
mation
DC1
DE1
00
Invalid parameter number
Access to an unavailable parameter
0
✓
01
Parameter value cannot be
changed
Attempting to have write access to a
parameter that cannot be modified
Subindex
✓
02
Value below lower limit or
above upper limit
Attempting to have write access with
a value out of range
Subindex
✓
03
Bad subindex
Attempting to access to a non-
available subindex in a string or array
parameter
Subindex
✓
04
Not an array
Attempting to use a subindex in order
to access a parameter without index
0
–
05
Incorrect data type
Attempting to have write access with
a value not corresponding to the data
type of the parameter
0
✓
06
Setting not allowed
Write access with a non-zero value
not allowed
Subindex
✓
07
Description element cannot be
modified
Attempting to have write access to a
description element that cannot be
modified
Subindex
–
08
reserved
–
–
–
09
No description data available
Attempting to access a non-available
description. The value is not
available.
0
✓
0A
reserved
–
–
–
0B
No usage rights
Attempting to have write access
without write permissions
0
✓
0C
reserved
–
–
–
0D
reserved
–
–
–
0U
reserved
–
–
–
0F
No text array available
Attempting to access a text array that
is not available
0
–
10
reserved
–
–
–
11
Request cannot be carried out
due to operating status
Access is temporarily not possible
0
✓
Byte
Designation
Description