2 Configuration
2.2 LEDs
18
DX-NET-PROFINET2-2
01/22 MN040062EN
www.eaton.com
The following tables show the meaning of the LED indicators for communica-
tion via PROFINET.
NS
The
NS
LED (network status) is used to indicate network statuses.
MS
The
MS
LED (module status) indicates the status of the DX-NET-
PROFINET2-2 communication interface.
Reversible vs. non-reversible error
Reversible errors can be resolved by a reset or by power cycling the supply
voltage (turning it off and then back on).
In contrast, fatal errors can only be reset by power cycling the supply voltage
or by changing the hardware configuration while the supply voltage is off.
LED status
Description
Off
No supply voltage or no connection to the IO controller available
Green flashing
Online, but no communication present
Green illuminating
The connection to the PROFINET network has been established; however, there
is a communication problem: The IO controller is in the stop state or there is a
synchronization error.
Red flashing
Fault detected
Flashes once: No station name assigned
Flashes twice: No IP address assigned
Flashes three times: Configuration error: Offline and online configurations do
not match
Illuminated red
Fatal error detected
LED status
Description
Off
No supply voltage or device not turned on.
Green flashing
Configuration error or module in standby mode.
Green illuminating
The connection to the PROFINET controller has been established.
Red flashing
A reversible error has occurred.
Illuminated red
A fatal error has been detected.
Green/red flashing
A firmware update is in progress. Do not switch off the device!