4 Commissioning
4.12 Acyclic data
DX-NET-PROFINET2-2
01/22 MN040062EN
www.eaton.com
73
620
0
P-30
P-30
STOP
rw
U16
Start mode
Defines the behavior of the drive relating to
the enable and also configures the automatic
restart after a fault.
For more information, please refer to the
manual for the basic device.
1
P-05
P-05
STOP
rw
U16
Stop mode
Determines the action taken by the drive in
the event of the drive enable signal being
removed.
For more information, please refer to the
manual for the basic device.
2
–
–
STOP
rw
U16
MainsLossStopControl
Stop mode in the event of a power failure.
For more information, please refer to the
manual for the basic device.
3
P-31
P-24
RUN
rw
U16
Digital Setpoint value
Reset Mode
Used to define the drive's behavior when it is
started and controlled using the keypad (P-
12/P1-12 = 1 or 2) or when it is controlled
using the UP and DOWN signals on the
terminals.
624
0
–
P-32
RUN
rw
WORD
Auto temperature
management
If this function is disabled, the drive will
switch off when there is an overtemperature
signal instead of automatically reducing the
switching frequency when the heat sink
becomes too hot.
625
0
P-38
P-39
RUN
rw
WORD
Parameter lock
Determines whether to lock the parameters
0: Not locked. All parameters can be
changed.
1: Locked. Parameter values can be
displayed, but cannot be changed. If a
remote keypad is connected, parameters
cannot be accessed by the remote keypad if
they are locked
1
–
–
RUN
rw
WORD
ParameterAdaptation
Motor parameter adaptation enable
0: deactivated
1: activated
PNU
PNU
Parameter
number
Access right
Data type
Name
Description
Index
Sub-
index
DC1
DE1
RUN/
STOP
ro/rw