4 Commissioning
4.12 Acyclic data
74
DX-NET-PROFINET2-2
01/22 MN040062EN
www.eaton.com
626
0
–
–
RUN
rw
U16
EnhancedGeneratorCon-
trol
Advanced generator control
0: deactivated
1: activated
1
P-06
P-06
RUN
rw
WORD
Energy?Optimizer
When energy optimization is activated, the
motor voltage is dynamically varied, depen-
dent on load. This results in reduced voltage
being applied to the motor on light load,
significantly reduce energy consumption.
This mode of operation is less suitable for
dynamic applications where the load condi-
tions can suddenly increase significantly.
2
–
–
RUN
rw
WORD
PLC Operation Enable
PLC function enable
0: deactivated
1: activated
3
–
P-31
RUN
rw
Overvoltage control
The overvoltage control function prevents
the drive from switching off when the motor
is feeding regenerative power back. When
disabled, the drive will trip “Over Voltage”
instead of automatically increasing the
motor ramp times.
627
0
–
–
RUN
rw
Fan control
630
0
–
–
RUN
rw
FieldbusRampControl
Ramp via field bus
0: disabled
1: activated
1
–
–
RUN
rw
WORD
Ramp Mode
Ramp selection when there is a preset speed
0: deactivated
1: activated
634
0
–
–
RUN
rw
U16
Standby Mode
Standby-time
0 is disabled
150
≙
15.0 s
635
0
P-33
–
RUN
rw
U16
Spin start enable
Rotary start enable/DC injection at enable
0: deactivated
1: activated
640
–
P-45
Fire mode function
650
2
–
P-19
RUN
rw
DI3 Logic
DE1 only:
This parameter defines the logic for input 3
when parameter P-27 is set to 1, 3, 5, 7, or 9
(external fault).
682
0
P-51
P-33
RUN
rw
U16
T-Memory Enable
When enabled, the motor thermal memory
retention function will save the calculated
motor thermal history on drive power down,
using this saved value as the starting value
on next power up.
If this function is disabled, the motor thermal
history is reset to zero on every power up.