4 Commissioning
4.11 Transparent Mode profile
58
DX-NET-PROFINET2-2
01/22 MN040062EN
www.eaton.com
4.11.2 Status words
Four status words are available.
Table 31:
Status words for the Transparent Mode profile
Status word 1
Status word 1 – “Transparent Mode” – contains general status and error
codes.
Device status and fault message information is provided in the status word
(bit 0 to bit 7) and fault word (bit 8 to bit 15).
The following table shows the structure of status word 1.
Table 32:
Status word 1 – Transparent Mode profile
If bit 0 is not active, check the mains voltage.
If no mains voltage is present, the bit = 0.
Telegram
Profile name / data
length
Output word (status) of variable frequency drive/variable speed
starter -> PLC
Vendor specific 999
Transparent Mode
4 x 16 bits
Status word 1
(FU status and
actual errors)
Status word 2
(VFD frequency
actual value)
Status word 3
(motor current)
Status word 4
(motor torque)
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
MSB
LSB
Fault word
Status word
→
The error codes can be found in the chapter “Errors and diag-
nostics”.
Bit
Description
Value = 0
Value = 1
0
Drive not ready
Ready for operation (READY)
1
Stop
Running operation message (RUN)
2
Clockwise rotating field (FWD)
Anticlockwise rotating field (REV)
3
No fault
Fault detected (FAULT)
4
Acceleration ramp
Frequency actual value equals setpoint
5
–
Zero speed
6
Speed control deactivated
Speed control activated
7
Hardware enable signal not present
Hardware enable signal present