5 Application example
5.7 Example program – DX-NET-PROFINET2-2 with TIA Portal
DX-NET-PROFINET2-2
01/22 MN040062EN
www.eaton.com
103
5.7 Example program – DX-NET-PROFINET2-2 with TIA Portal
The following chapter explains how to configure a program in the TIA Portal.
The hardware and software requirements are listed in detail. Basic program-
ming and configuration steps are not described in this section.
Detailed information can be found in the help tool of the TIA Portal.
5.7.1 Requirements for PLC control
In order to establish proper communication between a master (PLC) and the
DX-NET-PROFINET2-2 communication interface (slave), certain hardware
and software components are assumed to be present.
In this example, the following components are used:
•
Configuration PC with engineering tool (TIA Portal V15.1)
•
GSDML file for DX-NET-PROFINET2-2
•
PLC – Siemens
•
Switch (note: not mandatory)
•
PROFINET cable
•
DC1 variable frequency drive with
DX-NET-PROFINET2-2communication interface
•
Motor
5.7.2 Parameter setting and hardware enable
In order to enable control via PROFINET, the hardware enable and remote
access must be carried out via parameter P12.
→
section 4.4.1, “Hardware enable” describes how to enable
the variable frequency drive.
→
section 4.3, “Parameter settings” describes how to enable
the variable frequency drive for network communication.