www.eaton.com
Time constant D2
The values of the time data type D2 always refer to a specific, constant sam-
pling time T
a
. This time T
a
is the smallest sampling time (defined in PNU 962)
and is required here to evaluate D2.
The value for D2 can be calculated as follows: D2 = i x T
a
/16384
Table 40:
Time constant D2
Time constant T2
The values of the time data type T2 always refer to a specific, constant
sampling time T
a
. T
a
is the smallest sampling time (defined in PNU 962).
It is required here to calculate T2. The following applies: T2 = i x T
a
Table 41:
Time constant T2
Standard data types
Table 42:
Standard data types
Data type
Code
[dec]
Code
[hex]
Byte
Value range
Resolution
Time constant D2
120
78
1
0
≦
i
≦
(2 - 2
-14
) x T
a
2
-14
x T
a
Data type
Code
[dec]
Code
[hex]
Byte
Value range
Resolution
Time constant T2 (16 bits)
118
76
1
0
≦
i
≦
32767 x T
a
T
a
Time constant T2 (32 bits)
119
77
2
0
≦
i
≦
4294967295 x T
a
T
a
Data type
Coding
Integer8
2
Integer16
3
Integer32
4
Insigned16
6
Unsigned32
7
OctetString
10
→
For more information on data types, refer to the document
IEC 61158-5: 2003.