4.12.6 Error numbers
The following are the error numbers that are output via the “Transparent
Mode” profile under the input byte (see section "Input data").
Table 54:
Fault numbers
Error no.
Series
Message
(display)
Possible cause
dec
hex
DC1, DE1
Stop
There are no error messages present. There is no drive enable signal present.
00
00
DC1, DE1
no-Flt
Shown for P0-13 if there are no messages in the error register.
01
01
DC1, DE1
OI-b
Excessively high braking current
02
02
DC1, DE1
OL-br
Thermal overload on brake resistor.
03
03
DC1, DE1
O-I
Overcurrent at variable frequency drive output
04
04
DC1, DE1
I.t-trP
Motor overload.
05
05
DC1, DE1
PS-trp
Overcurrent (Hardware)
06
06
DC1, DE1
O.Volt
Overvoltage in DC link
07
07
DC1, DE1
VVolt
Undervoltage in DC link
08
08
DC1, DE1
O-t
Overtemperature at heat sink
09
09
DC1, DE1
V-t
Under-temperature
10
0A
DC1, DE1
P-dEf
The parameters’ default settings have been loaded.
11
0B
DC1, DE1
E-trip
External fault
12
0C
DC1, DE1
SC-ObS
Communication error with an external operating unit or with a PC
13
0D
DC1, DE1
FlT-dc
Excessively high DC-Link voltage ripple
14
0U
DC1, DE1
P-LOss
Incoming power phase failure (only for devices with a three-phase power supply)
15
0F
DE1
h O-I
Overcurrent at output, DC1 motor pick-up control fault
16
0A
DC1, DE1
Th-flt
Malfunctioning heat sink thermistor.
17
11
DC1, DE1
dAtA-F
Error in internal memory
18
12
DC1, DE1
4-20 F
The analog input’s input current does not fall within the specified range.
19
12
DC1…E1
dAtA-E
Error in internal memory
21
15
DC1…E1
F-Ptc
Motor PTC thermistor overtemperature
22
16
DC1…E1
FAn-F
The device’s internal fan is experiencing a fault
23
17
DC1…E1
O-hEAt
The measured ambient temperature exceeds the specified value.
26
1A
DC1…E1
OUt-F
Device output fault
40
28
DC1…E1
AtF-01
Motor identification failed
41
29
DC1…E1
AtF-02
Motor identification failed: The measured stator resistance is too large.
42
2A
DC1…E1
AtF-03
Motor identification failed: The measured motor inductance is too low.
43
C2
DC1…E1
AtF-04
Motor identification failed: The measured motor inductance is too high.
44
2C
DC1…E1
AtF-05
Motor identification failed: The measured motor parameters do not match.
49
31
DC1…E1
Out-Ph
A phase in the motor cable is not connected or has a discontinuity.
50
32
DC1…E1
Sc-FO1
No valid Modbus telegram was received within the specified time.
51
33
DC1…E1
Sc-FO2
No valid CANopen frame was received within the specified time.