4 Commissioning
4.11 Transparent Mode profile
DX-NET-PROFINET2-2
01/22 MN040062EN
www.eaton.com
57
Table 28:
Control word 1 – Transparent Mode profile
Control word 2
Table 29:
Control word 2 – Transparent Mode profile
Control word 3
Reserved
Control word 4
Table 30:
Control word 4 – Transparent Mode profile
Bit
Description
Value = 0
Value = 1
0
Stop
Operation
1
Clockwise rotating field (FWD)
Anticlockwise rotating field (REV)
2
No action
Fault Reset
3
No action
Coasting
4
Not used
5
No action
Quick stop (ramp 2)
6
No action
Fixed frequency FF1
7
No action
Overwrite setpoint value with 0
→
Bits 8 to 15 are not used.
CAUTION
When bit 0 and bit 1 are activated in input byte 0, the output of
the variable frequency drive/variable speed starter is activated.
Byte
Bit
Designation
Meaning
1
0, …, 7
Low
Setpoint
Setpoint input
The permissible values fall within a range of P-02 (minimum
frequency) to P-01 (maximum frequency)
In the application, the values will be scaled by a factor of 0.1.
2
8, …,
15 High
Byte
Bit
Designation
Meaning
1
0, …, 7
Low
Ramp time
Ramp time
The permissible values range from 0 to 60000.
In the application, the values will be scaled by a factor of 0.01,
i.e. 300
≙
3 s.
In this case, parameter P-12 must be set to 4 (only for the DC1
variable frequency drive).
2
8, …,
15 High