DYNISCO UPR800 Series Instruction Manual
Page | 33
parameter, or press the
RESET
key to go back to the active display. When set to Auto,
Group 4 Parameter LINE.R displays the detected Line Frequency.
8.2.5 Setting the Display Filter
Filtering is an electrical method of averaging the displayed values over a period of time to
arrive at a more legible display. Filtering helps to eliminate short duration transients and
spikes that may cause false or spurious readings.
To change or view the Main Analog Output Filter, press the
FUNC
key until
nonE
and
GROUP
show on the display. Press the
t
key until
2
shows in the upper display. Press
the
FUNC
key until the lower display changes to
DSP.FL
. Using the
u
or
t
keys, select
the amount of filtering desired, from none (
OFF
) to five seconds. When finished, press
the
FUNC
key to lock in the value and advance to the next parameter.
GROUP # FUNCTION
MNEMONIC
CHOICES
DEFAULT
Group 5
Primary Input
PI.TYP
Str, 0-20, 4-20, 0-5,
Str
Selection
0-10
Group 5
Secondary Input SI.TYP
OFF, tc, rtd, 0-20
Selection
4-20,
0-10,
str
Tc
Group 4
Shunt Calibration SHUNT
OFF, On
On
Group 4
Shunt Value
SHNT%
40.0 TO 100.0%
80.0%
Group 3
Input Full Scale
Value
PI.FSV 10
TO
99950
10000
Group 3
Input Low Scale
Value
PI.LSV
± 25% OF SFV
0
OF FS V
Group 3
Input Decimal
PI.DP
None, 1,2,3,4
None
Point Position
places
Group 3
Secondary Input Sl.TC
tc J, tc CA, tc L, tc n
tc J
T/C Type
Group 3
Alarm I Input
AI.LNK
OFF, Prl.ln, Sec.ln
Prl.ln
Channel Link
Group 3
Alarm I Type
AI.TYP
HI, LO, lnhib
HI
Group 3
Alarm 2 Input
A2.LNK
OFF, Prl.ln, Sec.ln
PrLIn
Channel Link
Group 3
Alarm 2 Type
ALTYP
HI, 10, lnhib
HI
Group 2
Zero Calibration
ZERO.C
OFF, On, CLEAr
OFF
Group 2
Span Calibration SPAN.C
OFF, On, CLEAr
OFF
Group 1
Alarm I Threshold AL1
TO 110%of span
40% of range of related
input
Group 1
Alarm 2 Threshold AL2
TO 110% of span
60% of range of related
input
In this example, these are functions necessary to allow operation of a pressure/temperature indicator with
two high alarms.