DYNISCO UPR800 Series Instruction Manual
Page | 66
Available:
Only if SI.TYP is different from ‘OFF’ and SI.FNC is equal to ‘diff.P’.
Upper display:
OFF
Lower display:
SPN.2.C
Range: Use
u t
keys to switch the upper display from OFF to On then
press FUNC key to start the zero calibration. It is also possible to
select the 'CLEAr' value to delete the field calibration and then
restore factory calibration.
Default value:
Full scale for linear input, 33.3mV for strain gage input
DISPLAY FILTER - Group 2
Available: Always
Upper display:
Time constant of the display filter (primary input).
Lower display:
DSP.FL
Range:
OFF, 0.4, 1, 2, 3, 4, 5 sec.
Default value:
0.4 sec.
ALARM 1 FILTER - Group 2
Available:
Only if A1.LNK is different than OFF.
Upper display:
Time constant of the alarm 1 filter.
Lower display:
A1.FL
Range:
OFF, 0.4, 1, 2, 3, 4, 5 sec.
Default value:
0.4 sec.
ALARM 2 FILTER - Group 2
Available:
Only if A2.LNK is different than OFF.
Upper display:
Time constant of the alarm 2 filter.
Lower display:
A2.FL
Range:
OFF, 0.4, 1, 2, 3, 4, 5 sec.
Default value:
0.4 sec.
ALARM 3 FILTER - Group 2
Available:
Only if A3.LNK is different than OFF.
Upper display:
Time constant of the alarm 3 filter.
Lower display:
A3.FL
Range:
OFF, 0.4, 1, 2, 3, 4, 5 sec.
Default value:
0.4 sec.
MAIN ANALOG OUTPUT FILTER - Group 2
Available:
Only if MO.TYP is different than OFF.
Upper display:
Time constant of the main analog output filter.
Lower display:
MO.FL
Range:
OFF, 0.4, 1, 2, 3, 4, 5 sec.
Default value:
0.4 sec.
SECOND ANALOG OUTPUT FILTER - Group 2
Available:
Only if SO.TYP is different than OFF.