DYNISCO UPR800 Series Instruction Manual
Page | 64
Range: Use
u t
keys to input the security code; if the selected code
matches the programmed code the parameters of the related security
level are unlocked. The unlock operation also unlocks the
parameters of the lower numbered groups, while the lock operation
locks all the parameters. To choose new security codes enter the
“Security Code Setting” operating mode. In order to re-lock the
different groups insert any number with the exception of the selected
codes.
ALARM 1 THRESHOLD - Group 1
Available:
Only if A1.LNK is different than OFF.
Upper display:
Alarm 1 threshold value
Lower display:
AL1
Range:
From low to high scale of the related input. The high limit may be
expanded to 110% of span.
Default value:
40% of range of the related input.
ALARM 2 THRESHOLD - Group 1
Available:
Only if A2.LNK is different than OFF.
Upper display:
Alarm 2 threshold value
Lower display:
AL2
Range:
From low to high scale of the related input. The high limit may be
expanded to 110% of span.
Default value:
60% of range of the related input.
ALARM 3 THRESHOLD - Group 1
Available:
Only if A3.LNK is different than OFF.
Upper display:
Alarm 3 threshold value
Lower display:
AL3
Range:
From low to high scale of the related input. The high limit may be
expanded to 110% of span.
Default value:
80% of range of the related input.
PRIMARY PRESSURE INPUT VALUE - Group 1
Available:
Only if SI.TYP is different from ‘OFF’ and SI.FNC is equal to ‘diff.P’.
Upper display:
Primary pressure input value
Lower display:
PI.VAL
Range: Read-only
parameter.
Default value:
Not applicable.
SECONDARY PRESSURE INPUT VALUE - Group 1
Available:
Only if SI.TYP is different from ‘OFF’ and SI.FNC is equal to ‘diff.P’.
Upper display:
Secondary pressure input value
Lower display:
SI.VAL
Range: Read-only
parameter.
Default value:
Not applicable.