DYNISCO UPR800 Series Instruction Manual
Page | 68
SECONDARY INPUT THERMOCOUPLE TYPE - Group 3
Available:
Only if SI.TYP is tc
Upper display:
Selected thermocouple type of temperature input.
Lower display:
SI.TC
Range:
tc J, tc CA, tc L, tc N, tc E, tc T. (thermocouple J, thermocouple K
(Cromel lumel), thermocouple L, thermocouple N, thermocouple E,
thermocouple T.)
Default value:
Thermocouple J
TEMPERATURE (SECONDARY) INPUT RTD TYPE - Group 3
Available:
Only if SI.TYP is RTD
Upper display:
Selected RTD type of temperature input
Lower display:
SI.RTD
Range: Pt100,
Pt500
Default value:
Pt100
ENGINEERING UNIT FOR SECONDARY INPUT - Group 3
Available:
Only if SI.TYP is tc or RTD
Upper display:
Selected type of temperature input engineering unit.
Lower display:
SI.C/F
Range:
Celsius or Fahrenheit
Default value:
°F
SECONDARY INPUT RANGE LOW - Group 3
Available:
Only if SI.TYP is 0-20, 4-20 or 0-10 and SI.FNC is equal to ‘tenp’
Upper display:
Secondary input range low
Lower display:
SI.LO
Range:
from -1000 to 3000
Default value:
0
SECONDARY INPUT RANGE HIGH - Group 3
Available:
Only if SI.TYP is 0-20, 4-20 or 0-10 and SI.FNC is equal to ‘tenp’
Upper display:
Secondary input range high
Lower display:
SI.HI
Range:
from -1000 to 3000
Default value:
1000
SECONDARY INPUT DECIMAL POINT POSITION - Group 3
Available:
Only when SI.TYP is 0-20, 4-20 or 0-10 and SI.FNC is equal to ‘tenp’
Upper display:
Secondary input range high
Lower display:
SI.DP
Range:
Use
u t
keys to select the position of the decimal point
Default value:
None
SECONDARY INPUT FULL SCALE VALUE - Group 3
Available:
Only if SI.TYP is different from ‘OFF’ and SI.FNC is equal to ‘diff.P’.