DYNISCO UPR800 Series Instruction Manual
Page | 76
Range:
0-20, 4-20, 0-10, -10.10, 0-5. 0-2mA, 4-2 mA, 0-10V, 0-5V.
Default value:
0-10V.
Note:
Proper terminal block wiring required
SECOND ANALOG OUTPUT SELECTION - Group 5
Available:
Only if second output is fitted
Upper display:
Type of second analog output selection
Lower display:
SO.TYP
Range:
OFF, 0-20, 4-20, 0-10, -10.10, 0-5. Disabled, 0-20mA, 4-20 mA, 0-
10V, -10-10V, 0-5V.
Default value:
0-10V
Note:
Proper terminal block wiring required
LOADING DEFAULT DATA - Group 5
Available:
Only if access to level C is allowed
Upper display:
OFF
Lower display:
DEFLT
Range:
Use
u t
keys to switch the upper display from OFF to On 5, then
press FUNC key to load the default data of the parameters belonging
to group 1, group 2, group 3, group 4 and group 5
12.6 Group 6 Parameters
SECURITY CODE - LEVEL A
Available:
Always
Upper display:
0, 1, On
Lower display:
CODE.A
Range:
Use
u t
keys to input the security codes. 0 means no security
code (all parameters related to level A are always unlocked). 1
means no security code (all parameters related to level A, level B and
level C are always locked). A number from 2 to 250 is the code for
level A protection
SECURITY CODE - LEVEL B
Available:
Only if CODE.A is 0 or On
Upper display:
0, 1, On
Lower display:
CODE.B
Range:
Use
u t
keys to input the security codes. 0 means no security code
(the parameters related to level A and level B are always unlocked).
1 means no security code (all parameters related to level B and level
C are always locked). A number from 251 to 500 is the code for level
B protection
SECURITY CODE - LEVEL C
Available:
Only if CODE.B is 0 or On
Upper display:
0, 1, On
Lower display:
CODE.C