DYNISCO UPR800 Series Instruction Manual
Page | 65
LOADING DEFAULT DATA - Group 1
Available:
Only if access to level A is allowed.
Upper display:
OFF
Lower display:
DEFLT
Range:
Use
u t
keys to switch the upper display from OFF to On 1, the
press FUNC key to load the default data of the parameters belonging
to Group 1.
GROUP ACCESS NUMBER
Available:
Always
Upper display:
OFF
Lower display:
GROUP
Range:
Use
u t
keys to switch the upper display from nonE to 1, 2, 3, 4 or
5 and then gain access to the parameters of the selected group by
pressing the FUNC key.
12.2 Group 2 Parameters
ZERO CALIBRATION - Group 2
Available:
Always
Upper display:
OFF
Lower display:
ZERO.C
Range:
to switch the upper display from OFF to On then press FUNC key to
start the zero calibration. It is also possible to select “CLEAr” value to
delete the field calibration and restore factory calibration.
Default value:
Zero
ZERO CALIBRATION FOR SECONDARY INPUT - Group 2
Available:
Only if SI.TYP is different from ‘OFF’ and SI.FNC is equal to ‘diff.P’.
Upper display:
OFF
Lower display:
ZER.2.C
Range: Use
u t
keys to switch the upper display from OFF to On then
press FUNC key to start the zero calibration.
It is also possible to select the 'CLEAr' value to delete the field
calibration and then restore factory calibration.
Default value:
Zero
SPAN CALIBRATION - Group 2
Available:
Always
Upper display:
OFF
Lower display:
SPAN.C
Range:
to switch the upper display from OFF to On then press FUNC key to
start the span calibration. It is also possible to select “CLEAr” value to
delete the field calibration and restore factory calibration.
Default value:
Full scale for linear input, 33.3mV for strain gage input.
SPAN CALIBRATION FOR SECONDARY INPUT - Group 2