19
6.6.2 Alarm and Control Relay Connector Pinout Table (864A)
Discretes 1–48
ALM
PIN
ALM
PIN
1
26
26
13
2
1
27
39
3
27
28
14
4
2
29
40
5
28
30
15
6
3
31
41
7
29
32
16
8
4
33
42
9
30
34
17
10
5
35
43
11
31
36
18
12
6
37
44
13
32
38
19
14
7
39
45
15
33
40
20
16
8
41
46
17
34
42
21
18
9
43
47
19
35
44
22
20
10
45
48
21
36
46
23
22
11
47
49
23
37
48
24
24
12
GND
25
25
38
GND/RTN*
50
Discretes 49-64, Relays 1-8, Analogs 1-6
ALM
PIN
Relays 1-8
49
26
RLY 1
9
34
50
1
RLY 2
10
35
51
27
RLY 3
11
36
52
2
RLY 4
12
37
53
28
RLY 5
13
38
54
3
RLY 6
14
39
55
29
RLY 7
15
40
56
4
RLY 8
16
41
57
30
FUSE
17
42
58
5
ADC
+
-
59
31
ADC 1
19
44
60
6
ADC 2
20
45
61
32
ADC 3
21
46
62
7
ADC 4**
22
47
63
33
ADC 5**
23
48
64
8
ADC 6**
24
49
GND
25
GND/RTN*
50
Analogs 7-8
ADC
+
-
7
B
A
8**
B
A
Table 7.B.
Alarm and relay connection pinouts for NetGuardian G5 864
RTN*
is the alarm return pin. Alarms on standard units are dry closure or ground closure. Most units will
have RTN internally tied to GND. However, special hardware assemblies may have RTN isolated from
GND. For details regarding your unit's hardware, please reference the product description appendix.
ADC
** channels 4, 5, 6, and 8 may be unavailable for external use. These analog channels are
sometimes configured in hardware for monitoring A and B power feeds, internal temperature, and
external temperature. For details regarding your unit's hardware, please reference the product
description appendix.
Summary of Contents for NetGuardian 832A
Page 9: ...4 Hardware kit containing a WAGO connector ...
Page 34: ...29 right ...
Page 39: ...34 Fig 6 9 1 Optional 66 block pinout for Discretes 1 24 ...
Page 40: ...35 Fig 6 9 2 Optional 66 block pinout for Analogs 1 8 Discretes 25 32 Relays 1 8 ...
Page 50: ...45 ...
Page 73: ...68 13 2 8 DSCP Configuration Configure your Serial Data Ports through the Edit Ports screen ...
Page 104: ...99 ...
Page 105: ...100 ...
Page 106: ...101 ...