14.1.1 System Alarms Display Map
Display Points
Alarm Point
Description
Solution
11
1-16
Control Relays Reserved by system for control relays.
Reserved by system for control relays.
17
Timed Tick
Toggles state at constant rate as
configured by the Timed Tick timer
variable. Useful in testing integrity of
SNMP trap alarm reporting.
To turn the feature off, set the Timed
Tick timer to 0.
18
Exp. Module
Callout
Alarm is triggered whenever an alarm
point from an Entry Control Unit (ECU)
is collected. A notification event may
be associated with the alarm to force a
call out or trap.
Disable Building Access Control (BAC)
by setting the BAC Unit ID to 0. If
Building Access is being used, then
investigate the ECU alarm source or
don’t associate notification with the
alarm event.
19
Network Time
Server
Communication with Network Time
Server has failed.
Try pinging the Network Time Server’s
IP Address as it is configured. If the
ping test is successful, then check the
port setting and verify the port is not
being blocked on your network.
20
Accumulation
Event
An alarm has been standing for the
time configured under Accum. Timer.
The Accumulation timer enables you to
monitor how long an alarm has been
standing despite system reboots. Only
the user may reset the accumulated
time, a reboot will not.
To turn off the feature, under
Accum.Timer, set the display and point
reference to 0.
21
Duplicate IP
Address
The unit has detected another node
with the same IP Address.
Unplug the LAN cable and contact your
network administrator. Your network
and the unit will most likely behave
incorrectly. After assigning a correct
IP Address, reboot the unit to clear the
System alarm.
22
WAN
Disconnected
WAN Top Board is present but the
WAN connection is not detected.
Check the back of the unit and confirm
WAN cable is connected and WAN
LED is solid green.
23
ECU
Emergency
Unlock
Set when both user-defined fire and gas
alarms occur.
Will clear when fire and gas alarms
clear. Feature can also be disabled if
"Emergency Unlock Enabled" is
unchecked from the web or NGEdit G5
interfaces.
24
D-Wire Sensor
Not Detected
A configured D-Wire Sensor is not
detected.
Check G5 D-Wire port and D-Wire
Sensor and confirm cable is plugged in.
Also make sure that configured ROM
ID's match the D-Wire Sensors plugged
in.
25
ECU Door
Violation
Door sensor has detected unauthorized
entry.
Verify integrity of door sensor. This
alarm is to alert of unauthorized
access.
26
Maintenance
Mode
Maintenance mode is currently active
for the server shutdown feature
Maintenance mode will timeout
according t othe amount specified by
the user in teh NGEdit "Server
Shutdown" tab.
27
DSCP Timeout The unit has not received a signal from
Check configuration of DSCP Poller.
Summary of Contents for NetGuardian 832A
Page 9: ...4 Hardware kit containing a WAGO connector ...
Page 34: ...29 right ...
Page 39: ...34 Fig 6 9 1 Optional 66 block pinout for Discretes 1 24 ...
Page 40: ...35 Fig 6 9 2 Optional 66 block pinout for Analogs 1 8 Discretes 25 32 Relays 1 8 ...
Page 50: ...45 ...
Page 73: ...68 13 2 8 DSCP Configuration Configure your Serial Data Ports through the Edit Ports screen ...
Page 104: ...99 ...
Page 105: ...100 ...
Page 106: ...101 ...