70
Configure your external DSCP devices through the Edit > DSCP screen
Advanced Configuration and Details:
Module Configuration
Module Address
High
4-byte identification address that is automatically acquired when the DSCP
device is synced with the NetGuardian.
Module Address
Low
4-byte identification address that is automatically acquired when the DSCP
device is synced with the NetGuardian.
Update Frequency
How often the wireless transmitter will wake from low-power mode and send a
measurement reading to the NetGuardian.
Type
The specific type of DSCP device (Propane Monitor, Track Monitor, etc...).
Level Detection (Propane Sensor Type Only)*
Read Frequency
This value determines how often the wireless transmitter will wake up and take
a measurement. If the value has dropped more than the Level Threshold, the
unit will exit low-power mode and send a reading to the NetGuardian.
Otherwise, it will send a reading only when the Update Frequency time has
passed. This allows you to acquire readings more often when the tank is being
actively emptied, at the expense of the higher battery usage. Input '0' to disable
this feature. This value must be smaller than the "Update Frequency" value.
Level Threshold
This is the percentage that the propane reading must drop between readings
to exit low-power mode and send the reading to the NetGuardian. (See above)
Generator Running Detection (Propane Sensor Type Only)*
Gen. Running
Frequency
When the specified alarm point (from Generator Point Reference) is set, the
timer value for Generator Running Frequency will override the timer value for
Update Frequency (under Module Configuration). This takes effect after the
next update.
Generator Point
Reference
Specify the Display and Point attached to Gen. Running Frequency. Input '0' to
disable this feature.
Summary of Contents for NetGuardian 832A
Page 9: ...4 Hardware kit containing a WAGO connector ...
Page 34: ...29 right ...
Page 39: ...34 Fig 6 9 1 Optional 66 block pinout for Discretes 1 24 ...
Page 40: ...35 Fig 6 9 2 Optional 66 block pinout for Analogs 1 8 Discretes 25 32 Relays 1 8 ...
Page 50: ...45 ...
Page 73: ...68 13 2 8 DSCP Configuration Configure your Serial Data Ports through the Edit Ports screen ...
Page 104: ...99 ...
Page 105: ...100 ...
Page 106: ...101 ...