38
Optional Hinged Wire-Wrap Back Panel
6.11
NetGuardian 832A G5
NetGuardian 864A G5
Fig. 6.11.1.
The hinged wire-wrap back panel is mounted on the mounting rack of the NetGuardian
WARNING
Alarm Pinout for NG864 is different than the NG832 and is not compatible with NG832
hinged panel termination units
Note:
The hinged wire-wrap back panel supports 18-26 AWG wire (solid). DPS Telecom recommends
using 24 AWG wire (solid).
The optional hinged wire-wrap back panel provides wire-wrap connections for the NetGuardian's alarms
and control relays. To connect alarms and control relays to the wire-wrap panel, follow these steps:
1. Mount the hinged wire-wrap back panel on the mounting rack of the NetGuardian.
2. Close the hinged back panel and lock in place by turning the black plastic locking swivel to the
vertical position.
3. Connect discrete alarms, analog alarms, and control relays to the two pin blocks.
Summary of Contents for NetGuardian 832A
Page 9: ...4 Hardware kit containing a WAGO connector ...
Page 34: ...29 right ...
Page 39: ...34 Fig 6 9 1 Optional 66 block pinout for Discretes 1 24 ...
Page 40: ...35 Fig 6 9 2 Optional 66 block pinout for Analogs 1 8 Discretes 25 32 Relays 1 8 ...
Page 50: ...45 ...
Page 73: ...68 13 2 8 DSCP Configuration Configure your Serial Data Ports through the Edit Ports screen ...
Page 104: ...99 ...
Page 105: ...100 ...
Page 106: ...101 ...