65
13.2.6 UnitKal
UnitKal settings are configurable from the TTY interface only. When used along with the UnitKal system,
the NetGuardian has the ability to remotely calibrate sensors at user definable time intervals. This
system removes the chances of human error when calibrating sensors. It helps to reduce the waste of
Calibration gas, and will offer better results when a sensor is in need of replacement. For more
information, view the TKP that is distributed with Sensor (D-PK-SENSR-12106.00001).
13.2.7 New! - TTY Command Mode
This command line mode offers an alternate way of configuring the NetGuardian G5. This interface is
scriptable, and is recommended for advanced users. Entries are NOT case sensitive.
Fig. 13.1.6
To enter Command Line mode, login to
the TTY, then press Ctrl+C.
Tips for using TTY Command Mode
·
To enter command mode, login to the TTY
interface and press Ctrl + C.
·
To view all acceptable operations, type
get help
,
then press Enter.
·
Invalid commands will return "Error" as the
response.
·
A
CRLF
is sent by the RTU following all
responses from the RTU.
·
Limited data validation is in place using this method. Use caution when setting variable values.
·
In some cases, you need to reboot the NetGuardian for new variable values to take effect.
·
Changing
REF1
,
REF2
,
DISP1
, or
DISP2
affects the
MAJOR, MINOR, OVER
, and
UNDER
alarm
thresholds. Changing any of these settings should be checked and re-established as required.
·
In the table below, variables (params) are noted in brackets.
Operation
Command
Params
Help
get help
None
Initialize NVRAM
init nvram {g2}
None
Write NVRAM
set nvram
None
Read NVRAM
get nvram
None
View System Up Time
get sysuptime
None
View Firmware Version
get prodid
None
Data Port Description
{get,set} dataport {1...9} desc
string {0...15} chars
Data Port Baud
{get,set} dataport {1...9} baud
{1200,300,600,1200,2400,48
00,
9600,19200,38400,57600,115
200}
Data Port Format
{get,set} dataport {1...9} wfmt
{8n1,8n2,7n1,7e1,7o1,8
o2,8o1}
Data Port RTS Head
(msec)
{get,set} dataport {1...9} rtshead
{0..255}
Data Port RTS Tail
(msec)
{get,set} dataport {1...9} rtstail
{0..255}
Data Port Type
{get,set} dataport {1...9} type
{off,tcp,ptcp,htcp,rtcp,udp,ch
an, crft,cap,ecu,sps8}
Summary of Contents for NetGuardian 832A
Page 9: ...4 Hardware kit containing a WAGO connector ...
Page 34: ...29 right ...
Page 39: ...34 Fig 6 9 1 Optional 66 block pinout for Discretes 1 24 ...
Page 40: ...35 Fig 6 9 2 Optional 66 block pinout for Analogs 1 8 Discretes 25 32 Relays 1 8 ...
Page 50: ...45 ...
Page 73: ...68 13 2 8 DSCP Configuration Configure your Serial Data Ports through the Edit Ports screen ...
Page 104: ...99 ...
Page 105: ...100 ...
Page 106: ...101 ...