18
6.6.1 Alarm and Control Relay Connector Pinout Table (832A)
Discretes 1–25
RTN
ALM
RTN
ALM
ALM 1
1
26
ALM 13
13
38
ALM 2
2
27
ALM 14
14
39
ALM 3
3
28
ALM 15
15
40
ALM 4
4
29
ALM 16
16
41
ALM 5
5
30
ALM 17
17
42
ALM 6
6
31
ALM 18
18
43
ALM 7
7
32
ALM 19
19
44
ALM 8
8
33
ALM 20
20
45
ALM 9
9
34
ALM 21
21
46
ALM 10
10
35
ALM 22
22
47
ALM 11
11
36
ALM 23
23
48
ALM 12
12
37
ALM 24
24
49
GND
25
50
Discretes 25–32
RTN
ALM
ALM 25
1
26
ALM 26
2
27
ALM 27
3
28
ALM 28
4
29
ALM 29
5
30
ALM 30
6
31
ALM 31
7
32
ALM 32
8
33
Control Relays 1–8
NO/NC
CO
CTRL 1
9
34
CTRL 2
10
35
CTRL 3
11
36
CTRL 4
12
37
CTRL 5
13
38
CTRL 6
14
39
CTRL 7
15
40
CTRL 8
16
41
FUSE
17
42
Analogs 1–6
ADC
+
–
ADC 1
19 44
ADC 2
20 45
ADC 3
21 46
ADC 4**
22 47
ADC 5**
23 48
ADC 6**
24 49
GND
25 50
Analogs 7–8
ADC
–
+
7
7– 7+
8**
8– 8+
Analogs 7–8
ANA 7 –
ANA 8 +
ANA 7 +
ANA 8 –
Table 6.6.1.A.
Alarm and control relay connector pinout for G5
Table 6.6.1.A shows the pinouts for the 50-pin connectors "Discretes 1–24" and "Analogs 1–6/Discretes
25–32/Relays 1–8," and the pinout for the four-pin connector "Analogs 7–8."
Note that the NetGuardian's control relays can be set for either Normally Open or Normally Closed
operation. By factory default, all control relays are set to Normally Open. You can reset all relays for
Normally Closed operation at the hardware level by resetting a jumper on the NetGuardian circuit board.
You can also configure the control relays individually, using either the Web interface or the NGEditG5
software utility.
For instructions on resetting control relays for Normally Closed operation, see the section titled
"Controls."
ADC
** channels 4, 5, 6, and 8 may be unavailable for external use. These analog channels are
sometimes configured in hardware for monitoring A and B power feeds, internal temperature, and
external temperature. For details regarding your unit's hardware, please reference the product
description appendix.
Summary of Contents for NetGuardian 832A
Page 9: ...4 Hardware kit containing a WAGO connector ...
Page 34: ...29 right ...
Page 39: ...34 Fig 6 9 1 Optional 66 block pinout for Discretes 1 24 ...
Page 40: ...35 Fig 6 9 2 Optional 66 block pinout for Analogs 1 8 Discretes 25 32 Relays 1 8 ...
Page 50: ...45 ...
Page 73: ...68 13 2 8 DSCP Configuration Configure your Serial Data Ports through the Edit Ports screen ...
Page 104: ...99 ...
Page 105: ...100 ...
Page 106: ...101 ...