25
6.6.8 Integrated Temperature and Battery Sensor (Optional)
Fig. 6.6.6.1.
The external temperature sensor
The optional integrated temperature and battery sensor monitors the ambient temperature and the
NetGuardian's power inputs. This option is available only if it was ordered with your NetGuardian. The
integrated temperature sensor measures a range of 32° F to 140° F (0° C to 60° C) within an accuracy
of ± 1°.
Sensor Function
Analog Input
Internal Temperature
analog input 4
Power Feed A
analog input 5
Power Feed B
analog input 6
External Temperature
analog input 8
Table 6.6.6.A.
Integrated sensor analog channels
Your integrated sensors each occupy one of the unit's 8 analog channels. Table 6.6.6.A lists the analog
channels used for the integrated temperature and battery sensor. Note that these options are factory
pre-set, based on your build options and cannot be adjusted.
6.6.8.1 Analog Step Sizes
Analog Step Sizes
:
Your Analogs are accurate to /- 1% of the analog range.
Analog Step Sizes and Accuracy
Input Voltage Range
Resolution (Step Size)
Accuracy
0-5 V
.0015 V
+/- .05V
5-14 V
.0038 V
+/- .14V
14-30 V
.0081 V
+/- .30V
30-70 V
.0182 V
+/-.70V
70-90 V
.0231 V
+/-.90V
Table 2.J.
Analog step sizes and accuracy
Summary of Contents for NetGuardian 832A
Page 9: ...4 Hardware kit containing a WAGO connector ...
Page 34: ...29 right ...
Page 39: ...34 Fig 6 9 1 Optional 66 block pinout for Discretes 1 24 ...
Page 40: ...35 Fig 6 9 2 Optional 66 block pinout for Analogs 1 8 Discretes 25 32 Relays 1 8 ...
Page 50: ...45 ...
Page 73: ...68 13 2 8 DSCP Configuration Configure your Serial Data Ports through the Edit Ports screen ...
Page 104: ...99 ...
Page 105: ...100 ...
Page 106: ...101 ...