67
Analog Polarity
{get,set} alg {1...8} polarity
0=Normal
1=Reversed
Analog Group Number
{get,set} alg {1...8} group {mju,mnu, mno,mjo}
{1...8}
Analog Reference 1
VDC
{get,set} alg {1...8} ref1
Number
Analog Reference 1
Display
{get,set} alg {1...8} disp1
Number
Analog Reference 2
VDC
{get,set} alg {1...8} ref2
Number
Analog Reference 2
Display
{get,set} alg {1...8} disp2
Number
Analog Deadband
{get,set} alg {1...8} deadband
{0.1...9.9}
Alarm Description
{get,set} alm {base,exp1,exp2,exp3} {1...64}
desc
string {0...48} chars
Alarm Polarity
{get,set} alm {base,exp1,exp2,exp3} {1...64}
polarity
0=Normal
1=Reversed
Alarm Trap
{get,set} alm {base,exp1,exp2,exp3} {1...64}
trap
0=trap disabled
1=trap enabled
Alarm Primary
Notification
{get,set} alm {base,exp1,exp2,exp3} {1...64} pri
{0...8}
Alarm Secondary
Notification
{get,set} alm {base,exp1,exp2,exp3} {1...64}
sec
{0...8}
Alarm Group
{get,set} alm {base,exp1,exp2,exp3} {1...64}
group
{1...8}
Global Trap IP Address
{get,set} trap {1,2} ipa
IP Address
Global Trap Format
{get,set} trap {1,2} format
{v1, v2c, v2cinf,v3}
LCD Display Mode
{get,set} lcdmode
{scroll,point}
LCD Delay Time (for
Point Mode)
{get,set} lcddelay
{1..60} {sec}
Examples
·
You want to find out how long this NetGuardian
has been running (since last rebooted.) Get
system uptime by typing
get sysuptime
, then
press Enter.
·
You want to see the alarm description for Base
Alarm 1. To see the description, type
get alm
base 1 desc
·
You want to set the Global Trap IP Address to
126.10.230.133. To enter this, type
set trap 1
ipa = 126.10.230.133
·
You want to change the LCD mode from Scroll
(default) to Point Mode. To change this, type
set
lcdmode = point
Summary of Contents for NetGuardian 832A
Page 9: ...4 Hardware kit containing a WAGO connector ...
Page 34: ...29 right ...
Page 39: ...34 Fig 6 9 1 Optional 66 block pinout for Discretes 1 24 ...
Page 40: ...35 Fig 6 9 2 Optional 66 block pinout for Analogs 1 8 Discretes 25 32 Relays 1 8 ...
Page 50: ...45 ...
Page 73: ...68 13 2 8 DSCP Configuration Configure your Serial Data Ports through the Edit Ports screen ...
Page 104: ...99 ...
Page 105: ...100 ...