76
Fig. 13.3.1.7.1.
Monitor and reset the Accumulator Timer
Field
Description
Display and Point
Reference
Indicates which alarm point is to be monitored.
Point Description
The user-defined description of the monitored alarm point.
Point Status
The current status of the monitored point.
Event Threshold
Amount of time allowed to accumulate before the system alarm,
“Accumulation Event” is triggered.
Note:
Maximum is 45 days.
Accumulated Time
The total time the monitored point has been in an ALARM state.
Accumulated Since
Indicates the last time the accumulation timer was reset.
Reset Accumulation
Timer
Selecting this option will reset the timer.
13.3.1.8 Monitoring DSCP Devices
View the status of the DSCP Analogs from the Monitor > DSCP screen
This Monitor > DSCP screen provides a description of each DSCP device alarm point state and each
DSCP device analog channel, the current reading, the units being read, alarm conditions (major under,
minor under, major over, and minor over), and the last instance of data transfer (Last Update) according
to your analog settings.