background image

Santa Clara, CA 95050
800.879.8585

Installation Instructions

U.S.Patents:

4,787,722

5,640,113

EW-105-24 and EW-205-24

Low Voltage Outdoor

Motion Sensors

180° & 270° PIR 

Speci

fi

cations

Voltage:

EW-105-24, EW-205-24  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .+24VDC
Current Consumption  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7mA

Power Supply  . . . . . . . . . . . . . . . .The Watt Stopper Power Pack or DM-105 module

B Series power packs supply power for up to 11 sensors.
BZ Series power packs supply power for up to 15 sensors.
DM-105 HID Bi-Level control module supplies power for up to 2 sensors.
DM-105-WP Outdoor HID Bi-Level control module supplies power for up to 2
sensors.

Coverage:

EW-105-24  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180°
EW-205-24  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270°

Time Delay Adjustment  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12sec.–16min.
Light Level Adjustment  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.5FC–200FC
Operating Temperature  . . . . . . . . . . . . . . . . . . . . . . . . . .-40° to 130°F (-40° to 55°C)
Mountable Locations  . . . . . . . . . . . . . . . . . . . . . . . .Pole, wall, ceiling or under eaves

IEC-IP-55 Raintight Rated

Summary of Contents for EW-105-24

Page 1: ...B Series power packs supply power for up to 11 sensors BZ Series power packs supply power for up to 15 sensors DM 105 HID Bi Level control module supplies power for up to 2 sensors DM 105 WP Outdoor...

Page 2: ...dule 6 Connecting to a DM 105 WP HID Dimming Module 6 TESTING AFTER INSTALLATION 7 DIAL ADJUSTMENTS 7 SECURITY OVERRIDE 9 TROUBLESHOOTING 9 ORDERING INFORMATION 10 WARRANTY INFORMATION 10 CAUTION READ...

Page 3: ...mounting heights ambient temperature and weather conditions DESCRIPTION The EW sensors are outdoor passive infrared PIR motion sensors rated for wet conditions They install onto standard round outdoor...

Page 4: ...r plate mounting as shown in the illustration on the right Horizontally mounted For horizontal mounting such as under eaves rotate the sensor housing as shown in the diagrams below Make sure that the...

Page 5: ...f sheltered locations preferred Aim motion sensor downward to limit sensing Mount motion sensor level Do not mount by vents or above lamps Install sensor no higher than 20 from ground Ideal mounting h...

Page 6: ...EW 205 24 have 3 wire connections to the power pack or DM 105 or DM 105 WP module See the descriptions and wiring diagrams that follow for connections to each specific power source RED 24VDC input to...

Page 7: ...om sensor to RED wire from the DM 105 WP cable BLACK common wire from sensor to BLACK wire from the DM 105 WP cable BLUE wire from sensor to WHITE wire from the DM 105 WP cable Control Output from Sen...

Page 8: ...t may be too high and the sensor s light level adjustment is keeping the sensor inactive Wait until daylight levels have reduced before testing again 5 See Dial Adjustments below for guidelines to adj...

Page 9: ...l toward the moon icon as desired this lowers the light level setting Remember the sensor must detect motion for lights to turn on The lights turn on high later in the evening The lights turn off low...

Page 10: ...vement in the coverage area the sensor should turn lights off low in 12 seconds Reset the time delay to the desired value If the lights do not turn off low have a person qualified to check high voltag...

Page 11: ...24 24VDC 270 Outdoor PIR Motion Sensor includes cover plate BZ 100 Power Pack 120 277VAC 60Hz 150mA 20A ballast or incandescent 1HP 120 240VAC B120E P Power Pack 120VAC 60Hz 150mA 20A ballast 13A inca...

Page 12: ...Putting a Stop to Energy Waste 2800 De La Cruz Boulevard Santa Clara CA 95050 USA Technical Support 800 879 8585 or 972 578 1699 www wattstopper com 03701r1 12 2003...