93
VII. System wiring
This chapter will introduce MVF2000 medium voltage drive wiring and spec requirements
for terminals.
7-1 Wiring of the primary loop
The typical wiring of the primary loop is as shown in Fig. 7-1, wherein the circuit breaker
MCB and the connection cables are provided by the user, and the filter cabinet is an optional
configuration.
Fig. 7-1 Typical wiring of the primary loop
7-2 Control power wiring
The user connects L and N of the control power to the No. 1 and 7 terminals of the
terminal block Y12, as shown in below table.
Y12
Definition
Description
1
L
600Vac max. 1ph., 50Hz
2
L
3
-
4
-
5
-
6
-
7
N
8
N
9
-
Spare
10
-
11
-
12
-
13
-
14
-
15
PE
Earthing
The power supply of the MVD is a double-loop power. Therefore, in the event of user
power failure, the power supply will switch to the auxiliary winding of the phase-shift
Summary of Contents for MVF2000 Series