threshold, output overload fault is generated.
Table 4-30 Output phase loss
ID
Parameter
Min
Max
Unit
Default
Description
P1110
Fault action
configuration: Output
Phase Loss
0
8
2
P1260
Fault duration time:
Output Phase Loss
0
65535
ms
80
P0068
1st threshold of
output phase loss
protection
0
100
%
25
Percentage of motor
rated current
P0198
2nd threshold of
output phase loss
0
40
%
5
Percentage of motor
rated current
If one phase of the output is disconnected in a duration time of P1260, output phase loss
fault is generated.
Table 4-31 Output grounding
ID
Parameter
Min
Max
Unit
Default
Description
P1111
Fault action
configuration: Output
Grounding
0
8
2
P1261
Fault duration time:
Output Grounding
0
65535
s
1
P0488
Active frequency of
output grounding
protection
0
50
%
10
Percentage of rated
frequency
P0197
Threshold of output
grounding
0
100
%
40
Start fault detection after exceeding the active frequency(P0488)
,
If one phase of the
output voltage is grounded, output grounding fault is generated.
Table 4-32 Output phase imbalance alarm
ID
Parameter
Min
Max
Unit
Default
Description
P1112
Fault action
configuration: Output
Phase Imbalance
Alarm
0
8
0
P1262
Fault duration time:
Output Phase
Imbalance Alarm
0
65535
s
30
P1010
Active frequency of
output phase
imbalance protection
5
100
%
5
P1011
Threshold of output
phase imbalance
0
1000
‰
15
Negative Ratio of
output voltage