Table 4-27 Input sequence fault
ID
Parameter
Min
Max
Unit
Default
Description
P1106
Fault action
configuration: Input
Sequence Fault
0
8
7
P1256
Fault duration time:
Input Sequence
Fault
0
65535
ms
500
While phase sequence of input voltage is incorrect in a duration time of P1256, input
sequence fault is generated.
Table 4-28 Output over current (software)
ID
Parameter
Min
Max
Unit
Default
Description
P1108
Fault action
configuration: Output
Over Current
(Software)
0
8
2
P1258
Fault duration time:
Output Over Current
(Software)
0
65535
ms
0
P0046
Threshold of output
over current
0
1000
%
160
Percentage of rated
motor current
P1069
Threshold of cell
output over current
100
200
%
130
Percentage of rated
power cell current
If the RMS value of three phase output current is higher than motor overcurrent
threshold(P0046) or power cell overcurrent threshold(P1069) in a duration time of P1258,
output over current(software) fault is generated.
Table 4-29 Output over load
ID
Parameter
Min
Max
Unit
Default
Description
P1109
Fault action
configuration: Output
Over load
0
8
2
P1259
Fault duration time:
Output Over load
0
65535
s
0
P0032
Duration time of
output overload
10
600
s
60
P0062
Initial detect current
of output over load
0
1000
%
105
Percentage of rated
motor current
P0088
Threshold of output
overload
100
1000
%
110
Percentage of rated
motor current
P0193
Detect time window
for output overload
protection
1
1200
s
600
While output current is below initial detect current of output over load(P0062), output
overload is not detected, and VFD can run continuously. Output overload condition is
115%(P88×P62) for 1min(P0032) every 10min(P00193). If the load of motor exceeds the