IV. Description of functional parameters
4-1 System parameters
Table 4-1 MVD basic parameter
ID
Parameter
Min
Max
Unit
Default
Description
P0005
MVD rated output
voltage
0
65535
V
6000
P0009
Level of continuous
mode
3
12
6
Power cells
configuration
per-phase
P0148
Software version of
DSP
31101
P0155
MVD rated input
voltage
0
65535
V
6000
P0174 Grid rated frequency
5000
6000
0.01Hz
5000
P0195
Transformer tap
position
95
105
%
100
P0239
High voltage power
on self diagnosis
time
220
500
0.1s
220
P0311
Delay time of cell
fault detection after
high power on
0
65535
ms
5000
P0312
Cell fault detection
time after high power
off
0
65535
ms
5000
P0498
Direction of output
voltage
0
1
0
1- Forward
1-Reverse
P1068
MVD rated output
current
20
2000
A
74
P1070
Delay time of input
fault detection after
high power on
0
65535
ms
500
P1915
Power on allowed
when fault is
detected by mian
controller
0
65535
0
999-Allowed
others-Forbidden
When the input voltage remains high, the transformer tap can be adjusted to +5%
position, and P0195
“Transformer tap position” should be set to 105%. When the input
voltage remains low, the transformer tap can be adjusted to -5% position, and P0195
“Transformer tap position” should be set to 95%.
When the output central point is in the left side, set P0498 “Direction of output voltage” to
0. When the output cen
tral point is in the right side, set P0498 “Direction of output