111
No tools or foreign objects are left in the cabinets.
All the cabinet doors including protective isolation facilities shall be closed and
ready in position.
5.
Restart the MVD: Operate according to the power-on operation instruction to see
whether there is any abnormity.
6.
Formulate daily record: All the maintenance information (including the revised
parameters) shall be recorded in the daily maintenance record:
Date and time.
Complete maintenance items according to the maintenance plan.
Any special situation or work (planed or unplanned spare parts replacement).
10-2 Maintenance plan
To ensure the long-term steady operation of the equipment, it is necessary for the user to
conduct correct operation and maintenance. The daily protective maintenance and
inspections shall be conducted in a planned way. In addition to the emergency system
maintenance, predictive maintenance shall be conducted, including daily, weekly, monthly,
quarterly and annual inspections and maintenance.
1. Daily maintenance
Maintenance item
Duration
Maintenance detail
Environment
‐
Daily
MVD indoors temperature should in the range of 0
~
40
℃
,
25
℃
is apporiate
Humidity is lower 95%
,
no condensation
Air passage type MVD should check the condition of
ventilation
Recommanded record the environment paramenter daily,
check if there is abnormal condition. If abnormal, check the air
condition of air duct.
Operating parameter
‐
Daily
Check the MVD input voltage is correct or not
Check the MVD operating parameter is normal or not,
and warning / fault record
Check the temperature of trans former is in the normal
range or not
(
temperateure shown on HMI
can’t over
90
℃
)
.
MVD overall
‐
Daily
Check whether MVD is normal, such as oeperating indicator
does not light, abnormal sound, vibration, fire or smell.
Cooling fan
‐
Daily
Check whether there is abnormal vibration and sound.
Check if there is cooling fan failure and cooling fan power
supply drop alarm.
Filter
‐
Daily
Check whether the filter is blocked.
Check whther there is air pressure alarm
Recommanded clear the filter at least once 1 week. If the dust
is heavy, the clear duration should be shorten. To disassemble
the filter, please check Maintenance 1.
Recommanded clear method: gently tap it outside the room to
drop off dust. Blow with compressed air slightly. Otherwise