voltage
” to 1.
Table 4-2 Power cell parameter
ID
Parameter
Min
Max
Unit
Default
Description
P0388
Power cell rated
input voltage
300
800
V
690
P0867
Power cell rated
output current
10
2000
A
70
P0882
Upper limit of Power
cell DC voltage filter
100
200
%
120
P0883
Lower limit of Power
cell DC voltage filter
0
100
%
80
Table 4-3 DCS configuration
ID
Parameter
Min
Max
Unit
Default
Description
P0246 Fault output type
0
1
1
0-Pulse
1-Level
P0788 Start and stop mode
0
1
0
0-Normal start and
stop
1-Start-up with
upstream switchgear
control
P0789 Start signal definition
0
2
0
0-Pulse signal
1-Level signal
(On-start; Off-free
stop)
2-Level signal
(On-start;
Off-deceleration
stop)
Table 4-4 Running mode
ID
Parameter
Min
Max
Unit
Default
Description
P0601 Running mode
1
4
1
1-VF
2-SVC
3-SLVC
4-Grid
Table 4-5 Sample configuration
ID
Parameter
Min
Max
Unit
Default Description
P0006
Coefficient of input
voltage
0
65535
0.001
1000
P0007
Coefficient of output
voltage
0
65535
0.001
1000
Summary of Contents for MVF2000 Series