Table 4-23 Input power loss
ID
Parameter
Min
Max
Unit
Default
Description
P0484
Voltage threshold of
input power loss
100
900
‰
700
Thousanth ratio of
rated input voltage
P1332
Delay time of input
power loss detection
0
65535
ms
500
P1333
Incoming time of
input voltage
0
65535
s
0
If the voltage values of input three phases are all lower than voltage threshold of input
power loss(P0484),
and MCB is still closed after the delay time
(P1332)
,
input power loss
fault is generated.
Table 4-24 Input under voltage
ID
Parameter
Min
Max
Unit
Default
Description
P1103
Fault action
configuration: Input
Under Voltage
0
8
1
P1253
Fault duration time:
Input Under Voltage
0
65535
ms
500
P0047
Threshold of input
under voltage
10
100
%
90
Percentage of rated
input voltage
While MCB is close, if the RMS value of three phase input voltage is lower than
threshold of input under voltage(P0047) in a duration time of P1253, input under voltage
fault is generated.
Table 4-25 Input over voltage
ID
Parameter
Min
Max
Unit
Default
Description
P1254
Fault duration time:
Input Over Voltage
0
65535
ms
0
P0054
Threshold of input
over voltage
100
120
%
110
Percentage of rated
input voltage
While MCB is close, if the RMS value of three phase input voltage is higher than
threshold of input over voltage(P0054) in a duration time of P1254, input over voltage
fault is generated.
Table 4-26 Input grounding
ID
Parameter
Min
Max
Unit
Default
Description
P1105
Fault action
configuration: Input
Grounding
0
8
7
P1255
Fault duration time:
Input Grounding
0
65535
100ms
50
P0877
Voltage threshold of
input grounding
0
100
%
70
If one phase of the input voltage is grounded in a duration time of P1255, input
grounding fault is generated.